Code 1Danger Present: Live conductors have no insulation, An accessory is badly damaged, Exposed live part are accessible to touch, a fuse carrier or circuit-breaker is missing from a CU with no blanking plate in place, terminations or connections have no (or damaged) barriers or enclosures, Code 2 Potentially Dangerous: Utility water pipe used as the means of earthing, CSA of main earthing conductor too small, Absence of main protective bonding, Absence of earthing at socket outlet, A ‘borrowed neutral’, for example where a single circuit neutral is shared by 2 circuits, Code 3 Improvement Recommended: Absence of RCD protection for socket outlets used outdoor, Absence of RCD protection for cables ≤ 50mm deep in a wall, Absence of RCD for circuits in a bathroom, Sheath of multicore cable not entering an enclosure, Absence of ‘Safety Electrical Connection — Do Not Remove notice, Further Investigation: Main protective bonding to gas, water or other service pipe inaccessible for inspection, Switch lines not identified as line conductors at terminations, Installation not divided into an adequate number of circuits, Use of unsheathed flex for lighting pendants, Absence of a reliable earth connection to a recessed metallic back box,
0%
EICR Codes
Share
Share
Share
by
Wlcconstruction
Edit Content
Print
Embed
More
Assignments
Leaderboard
Show more
Show less
This leaderboard is currently private. Click
Share
to make it public.
This leaderboard has been disabled by the resource owner.
This leaderboard is disabled as your options are different to the resource owner.
Revert Options
Group sort
is an open-ended template. It does not generate scores for a leaderboard.
Log in required
Visual style
Fonts
Subscription required
Options
Switch template
Show all
More formats will appear as you play the activity.
Open results
Copy link
QR code
Delete
Continue editing:
?